|
|
Autogrow
Systems Ltd |
|
Humidity Control in
greenhouses |
|
What
is Humidity? Humidity refers to the quantity of water present in the air as vapour. If we set up a fogging system (or boil some water) to continually put water fog/vapour into a closed greenhouse the humidity will continually climb until a point is reached where it is impossible to add any more water vapour. This is called the saturation point or 100% relative humidity (RH). More water can only be added after an equal amount has condensed out of the air. The condensation will occur on the coolest surfaces available. If no cool surfaces are available then the fog/vapour droplets would combine and fall as water drops onto the floor ie it will rain. Humidity is most often measured as Relative Humidity (RH). This represents the amount of humidity present in the air as a percentage of the maximum possible. 100% RH represents saturation of the air and 0% RH represents absolutely dry air. Greenhouses often operate between 60% and 80% RH If you take a fixed volume of air with a fixed amount of moisture in it and change its temperature the RH will change dramatically. By heating air you tend to dry it out and the RH falls. In fact, increasing the temperature by as little as 10oC nearly doubles the water holding capacity of the air. This means that if the RH was 100% at a temperature of say 10o C then heating to 20o C would lower the RH to little more than 50%. Conversely, by cooling air the RH
rises and eventually it will reach saturation condensation will occur.
The temperature at which this occurs is called the Dew Point.
This is another important measure of humidity. (Note that
although it is a measure of humidity it is expressed in deg C).
Condensation will appear on any surface whose temperature is at,
or below, the dew point. Normally,
the roof and walls cool down first and this is where you will notice
most condensation. 2) Plants transpire a lot of moisture into the air. A tomato vine will transpire about 0.2L per hour into the air in summer. That’s almost 2L per day per plant. For a 2000 m2 house with 2.5 plants per m2 that’s a total of 5000 plants and nearly 10,000L per day of transpiration to get rid of. Plants are the primary humidifiers/coolers of greenhouse air. It is therefore vital to provide adequate irrigation on hot, sunny days. It all has to go out the window or
else it has to condense on something. 1) Humidity too high.
Usually at night or in winter when vents are closed the humidity will build up.
2)
Humidity too low Typically in hot dry weather with vents wide open.
So,
what level of humidity is ideal? The
converse is also true ie when temperatures are low then RH should be
reduced. At low temperatures
the plant will tend to reduce transpiration (with consequently reduced
growth) but by reducing the RH this will tend to raise transpiration
back up again. The
grower with simple humidity controls can address this temperature
dependence by reducing RH set points during winter and raising them in
summer. The
following table gives you some idea of the ideal level of RH for a
typical crop.
You
can see from the table that the higher the temperature is, the higher
the humidity should be. The above makes it difficult to specify
control parameters as different RH settings are required at different
temperatures. Another
measure called VPD is gaining popularity in the greenhouse industry as
it combines both temperature and humidity effects in a way that better
reflects how the plant “feels”.
VPD stands for “vapour pressure deficit” and while we won’t
go into the physics of it here it is worth noting that it represents the
lack (or deficit) of moisture in the air.
Consequently, the numbers run in the opposite direction to RH ie
a VPD of zero represents saturation or 100% RH and larger VPD numbers
represent increasing “dryness”.
If this happens on the greenhouse
roof and if this a good design so that dripping is minimized with
internal gutters that collect and lead away the condensation then this
can actually help to reduce the humidity in the air. However, the RH will still be very
high and will be even higher inside the crop canopy.
Radiant heating applied low down by pipes running amongst the
crop will help to warm the plants and avoid condensation directly on the
crop. Gentle fan stirring
will also help to ease the humid air out of the crop canopy where it
will rise and condense out on the cold roof.
If applied correctly, this can be a reasonably cost effective
method of humidity control. Now imagine that we have a double skinned greenhouse or a single roof skin with a thermal screen below. The humidity from the crop is now trapped below the screen (or inside cover) and no longer has such a cold surface to condense on. If the humidity gets very high it will only need to find a surface which is a few degrees cooler to start condensing. This situation is not quite so easy to deal with. On the positive side, the thermal reflecting screen will help to prevent the crop from loosing radiant heat. Always remember that transpiring plants will be adding water vapour to the air which must go somewhere or the RH will continually climb. 1)
Ventilate to remove the moist air Or some combination of the above. Scenario
1 – moderate temperature
ie temperature either in the opening range of the vents or close to
either side of the opening range. a) high humidity The strategy normally used here is to change the venting set point a little to cause the vents to open sooner (or wider) in order to allow the humid air to escape and to be replaced by drier, cooler air. Another simple strategy that can be employed to lower high humidity is to increase the heating (raise the heating set point). This is especially effective where the heat is applied inside the crop canopy. In extreme cases the heating and venting setpoints can be overlapped so that heating and some venting occur simultaneously. The cost benefits of doing this must be carefully weighed up by the grower. b) low humidity The strategy normally used for low humidity is to change the venting set point a little to cause the vents to open later (or less wide) in order to reduce excessive humidity. Obviously, there is a limit to what
can be achieved (without cooking or freezing the crop) but these passive
control strategies are very low cost and use little energy. Scenario
2 – High humidity in very cold conditions In an attempt to save energy a mode
of operation called “purging” may be used to reduce high humidity.
Here, the heating setpoint is raised to help dry air and the crop
and then periodically the vents are cracked open to allow the warmed
humid air to float up and out and allow cooler air to enter.
Surprisingly, this works even when the outside air is quite damp
providing heating is used as the rise in temperature inside will dry the
incoming fresh moist air. However,
the transpiring crop will eventually bring the RH back up again and the
vents will need to be cracked again.
Providing the crop is not over sensitive to the sudden drops in
temperature this is a viable low cost method of humidity control. Where
crops are sensitive to sudden changes in temperature an alternative is
to set a “minimum crack size” for the leeward vent and to just
elevate the heating set-point. There
is normally an override on the minimum vent crack so that if the
temperature drops below a certain value the vents will fully close –
this is sometimes referred to as “frost protection” Scenario
3 – High humidity in very cold conditions with a threat of
condensation on crop at sun-rise. This
is the situation where the sun comes up after a cold night and the
leaves (at least on the sunny side) warm quickly and start transpiring.
The rest of the plant is still cold and below the dew point of
the now moist air. Condensation
can occur and in some weather conditions the fruit may stay wet for some
time – long enough for disease to set in. A
reflective thermal screen will help to prevent the crop from loosing
radiant heat to a clear sky but will also trap the humidity down close
to the crop. By cracking the
screen periodically, say 10% open, the humidity will escape to the upper cavity away
from the crop. A controller
that automates this is very useful. A
further strategy that may be used to avoid morning condensation on the
crop is called pre-dawn heating. As
the name suggests, the heating set point is gradually ramped up in the
early hours of the morning so that by dawn the temperature of the plant
fruit, stems and leaves are only a little below the day-time venting
temperature. Modern
controllers automatically calculate the time to start ramping the
heating up in order to achieve the desired dawn temperature. Scenario
4 – Low humidity in hot conditions In this situation it is not
desirable to try to close the vents as the temperature would rapidly
build up and harm the crop. The
only option is to apply fogging or other humidification.
Luckily, heat and low humidity usually come together and fogging
will address both of these issues. As
the fog turns to vapour, it takes a lot of heat out of the air and can
result in considerable temperature drop – 5oC not being
uncommon. Of course it also
adds humidity at the same time which is exactly what is required to
maintain a reasonable VPD.
Foggers with a very small droplet size are the most desirable as
the fog vaporizes almost instantly without any wetting of nearby plants.
Fog controllers with an automatically adjustable “puff” size
gives the best results. These
give out small puffs of fog when the temperature or humidity error is
small and larger sized puffs as the error increases. Manual
or automatic Although it is possible to
implement some of these ideas in a manually operated greenhouse, to get
the most consistent and accurate control a
|
||||||||||||||||||||||||||
|
|